Description

CUTLER-HAMMER HMCPS007C0C Magnetic Motor Circuit Protector Description

Overview

CUTLER-HAMMER HMCPS007C0C is a Series C magnetic-only motor circuit protector (MCP) under Eaton Cutler-Hammer brand. This motor circuit protector provides instantaneous short-circuit protection for three-phase motor branch circuits, and the motor circuit protector must pair with a separate overload relay to achieve complete motor protection. The motor circuit protector is widely matched with contactors to form integrated motor starters in North American control panels.

Features

CUTLER-HAMMER HMCPS007C0C adopts magnetic instantaneous trip design without bimetallic overload trip, so it focuses on suppressing sudden short-circuit fault current. This motor circuit protector supports adjustable current setting from 1.5A to 5.7A, with fixed magnetic trip threshold at 13 times the rated current. This motor circuit protector is compatible with Cutler-Hammer contactor series, and optional auxiliary contacts can be installed to feedback trip status to PLC and alarm systems. It has a rugged molded case housing and high short-circuit breaking capacity, complying with UL489 standard. The model suffix S stands for steel terminal collars variant, and it carries UL, CSA and CE certifications for industrial control cabinet applications. It is suitable for Type 1 coordination to limit arc damage to contactor contacts during fault events.

Technical Parameters

CUTLER-HAMMER HMCPS007C0C belongs to Series C MCP family. It is a 3-pole magnetic-only protector, current adjustment range 1.5–5.7A. Rated voltage up to 600VAC. Magnetic trip threshold fixed at 13×In. It uses screw terminal connection with steel collars, standard DIN rail mounting. It only provides short-circuit protection; overload protection needs independent thermal overload relay.

Working Principle

CUTLER-HAMMER HMCPS007C0C monitors the current of the motor branch circuit continuously. When short-circuit fault occurs, huge current generates strong instantaneous magnetic force inside the motor circuit protector to pull the trip coil and open the main contacts rapidly. For normal overload conditions, this MCP will not trip, and overload protection is undertaken by the matched overload relay. Once tripped, manual reset is required after fault clearance. Auxiliary contacts change state synchronously to transmit fault signals to the control system for interlock and alarm action.

Application Fields

CUTLER-HAMMER HMCPS007C0C is widely used for small pumps, fans, conveyors and automated machinery in North American style motor starter control panels. It serves as short-circuit protection branch unit for three-phase motor loads. This motor circuit protector is a common replacement spare part for maintaining Eaton Cutler-Hammer legacy motor control systems.


Get a Quote