Honeywell 51304718-325 16‑Channel Non-Isolated HART 4–20mA Analog Output FTA
Description
2. Model Definition
51304718: Base model for 16-channel non-isolated HART analog output FTA
-325: Ultra heavy-duty reinforced PCB protection grade
Thick multi-layer full-board military-grade conformal coating with exceptional resistance to extreme humidity, conductive heavy dust and moderate-severity corrosive chemical vapors
Multi-stage composite high-energy bidirectional surge absorption stack (TVS+transient absorber), drastically higher transient withstand energy than all -200 and lower suffix models
Three-stage fully symmetrical cascaded RC differential EMI filter, precision calibrated for ultra-high-noise zones with massive VFD clusters, large MCC banks and medium-voltage switchgear, zero attenuation to HART FSK carrier waveform
Global unified common ground bus for all 16 channels; no independent galvanic isolation barriers between individual output loops
Oversized high-current reinforced flyback freewheeling diode arrays to fully dissipate extreme back-EMF spikes from large inductive heavy-load actuator coils
Ultra-precision ultra-tight tolerance series damping resistors for perfectly uniform full-range 4–20mA linear stroke response across all 16 channels
Extra-wide ultra-thick reinforced plastic channel partition baffles to completely eliminate inter-channel analog leakage and HART signal crosstalk
3. Technical Specifications
Channel Count: 16 common-ground output channels, no per-channel galvanic isolation
Compatible Field Devices
Two-wire heavy-duty HART smart valve positioners, high-load electro-pneumatic HART I/P transducers, large linear/rotary HART modulating actuators
Backward compatible with conventional non-HART 4–20mA pneumatic positioners and standard I/P converters
FTA Structure: Passive non-isolated termination board with no internal power supply; integrated per-channel low-distortion HART coupling, three-stage symmetrical differential filtering, multi-level ultra-high-energy surge protection and heavy-duty inductive kickback suppression
PCB Protection: Thick multi-layer military reinforced conformal coating; flammability UL94 V0
Terminal Type: Compression screw terminals compatible with solid/stranded copper wire up to 14 AWG; each channel owns independent Ch+ / Loop– terminal pair connected to unified global ground bus
Form Factor: Standard B-size footprint, snap-on DIN rail installation for 35 mm standard rails
Operating Ambient: 0℃ ~ +60℃ indoor control cabinet; humidity, dust and moderate-severe corrosion tolerance far exceeds -200 and lower grades; tolerates intermittent light salt mist; continuous heavy coastal salt fog requires upgrade to -375 grade
Circuit Architecture Parameters
Three-stage symmetrical low-pass differential filtering suppresses extreme industrial EMI without distorting HART waveform or 4–20mA analog drive amplitude
Multi-level composite bidirectional surge stack clamps positive/negative extreme transient high voltage on every shared-ground output loop
Shared common ground design; ground potential discrepancies between field and DCS will still induce slight stroke drift and minor HART instability (isolated FTA required for multi-ground sites)
Ultra-tight precision tolerance damping resistors completely eliminate valve hunting and stabilize full-span 4–20mA linear output performance
Oversized high-current flyback diodes rapidly absorb extreme back-EMF energy generated by large heavy inductive actuator coils
Ultra-thick baffles fully block inter-channel analog bleed and cross-channel HART signal interference
Redundancy Support: Fully compatible with primary/standby redundant non-isolated HART AO IOP; hot-swap FTA replacement allowed without process shutdown
Approximate Unit Weight: 0.363 kg
4. Interface & Communication Configuration
Inner IOP Connection: Locking heavy-duty flat ribbon cable directly mates to non-isolated HART AO IOP pin headers. Reinforced multi-point heavy-duty cable strain relief prevents pin header deformation or fracture under long-term sustained tension of lengthy multi-core field control wiring harnesses.
Field Outer Terminals: Independent Ch+ / Loop– terminals for each two-wire actuator loop; all loops reference one unified ground bus matched to DCS control ground potential.
Signal Mechanism: 4–20mA DC analog drive signals overlaid with FSK HART digital signals via frequency division; low-distortion passive HART coupling integrated per channel circuit.
HART Access: No dedicated auxiliary communication port; handheld HART communicator clamps directly across Ch+ and Loop– field terminals for commissioning, calibration and diagnostic data reading.
5. Core Functions
Common-ground mixed HART/standard heavy-load actuator drive: Cost-effective single-ground layout supporting mixed deployment of heavy-duty HART smart actuators and conventional non-HART 4–20mA loads within the same cabinet.
Three-stage symmetrical ultra-heavy EMI noise rejection: Suppresses extreme intense electromagnetic interference from large VFD systems, MCC banks and medium-voltage switchgear to eliminate valve hunting, severe setpoint fluctuation and frequent HART communication retries.
Multi-level ultra-high-energy surge & short-circuit fault protection: Withstands lightning-induced line transients, high-magnitude equipment startup surges and field short-circuit high voltage to protect expensive sensitive IOP output power semiconductors and heavy-duty field actuators.
Heavy-duty uniform inductive load protection: Oversized flyback diode arrays evenly safeguard all channels from coil back-EMF damage for long-term stable continuous operation.
Consistent channel linearity & stable HART synchronization: Ultra-precision matched passive components deliver identical valve stroke response and reliable HART handshake across all 16 channels to reduce bulk calibration workload.
Redundant hot-swappable operation: Seamlessly synchronizes with primary/standby IOP switching logic; single-channel disconnection and troubleshooting do not impact operation of remaining 15 control loops.
6. Application Scenarios
Applicable Industries
Large integrated petrochemical complexes, heavy-duty chemical synthesis plants, combined heat & power generation stations, massive oil & gas refineries, pulp & paper mills, high-humidity industrial wastewater treatment, medium-to-high humidity heavy-batch pharmaceutical manufacturing lines, inland coastal sites with intermittent light salt mist
Typical Control Loops
Critical emergency safety shutoff system heavy-duty HART smart valve positioners
High-pressure large-flow process throttle HART modulating actuators
Oversized furnace draft air damper high-load HART I/P transducers
High-volume process blending control valve heavy smart HART positioners
High-pressure reduction large modulating HART actuators
Ideal for single-ground plant layouts, ultra-dense VFD heavy-noise process areas, cabinets with persistent extreme high humidity and heavy conductive dust accumulation, atmospheres containing moderate-to-severe acidic/alkaline volatile vapors, inland sites with occasional light salt mist. Not suitable for offshore platforms or coastal locations with continuous heavy salt fog exposure (upgrade to -375 for full salt fog resistance).
7. Wiring Standards
Two-wire actuator wiring: Actuator positive → FTA Ch+, actuator negative → FTA Loop– (shared ground bus); reversed polarity reduces kickback suppression efficiency and impairs HART waveform integrity.
Cable specification: Heavy-duty shielded twisted-pair instrument cable for all field wiring runs; cable shield grounded solely at DCS cabinet FTA side with field equipment end ungrounded to fully suppress ground loop noise.
Power cable segregation: Physically separate HART analog control cables from high-voltage AC power, MCC and VFD output wiring to minimize capacitive and inductive EMI coupling interference.
8. Incompatible Hardware
All isolated AI/AO FTAs (51304644, 51304640, 51304648, 51304650), non-isolated HART AI (51304685), non-isolated non-HART AI (51304672), non-isolated non-HART AO (51304690), discrete DI/DO termination boards, TC/RTD dedicated FTAs, pulse counter termination blocks and serial communication terminal assemblies cannot be paired with this non-isolated HART AO IOP card.
Get a Quote