Honeywell 51304427-200 Relay Digital Output FTA
June 10, 2026

Honeywell 51304427-200 Relay Digital Output FTA

1. Basic Model Information Part Number: 51304427-200 Common Model: MU-TDOR62 Full Name: Relay Digital Output Field Termination Assembly, CE Screw Terminal Applicable System: Honeywell TDC3000 / TPS UCN DCS Control System Matching Main Card: MU-DOR62 Relay Output IOP Card

Description

2. Product Function Description

This relay-type digital output FTA terminal board is matched exclusively with MU-DOR62 main IOP card. Built-in isolation relays convert low-voltage logic signals from DCS main control card into isolated dry contact signals to drive field AC/DC loads. It provides complete galvanic isolation between cabinet internal circuits and field equipment, eliminating ground loop interference and back EMF damage to main control cards. Equipped with CE-certified anti-loose screw terminals, it ensures stable wiring under high-vibration working conditions for chemical, power and oil & gas continuous production sites.

3. Core Electrical Technical Specifications

  1. Output Type: Isolated dry relay contact output

  2. Max Load Rating: 240VAC / 125VDC per channel

  3. Channel Configuration: 16 relay output channels, fully compatible with MU-DOR62 IOP

  4. Terminal Structure: CE standard screw terminal, anti-vibration and anti-loosening

  5. Anti-interference Design: On-board TVS surge suppression to absorb inductive load counter electromotive force

  6. Power Supply: Powered by DCS rack backplane

  7. Operating Ambient Temperature: -40℃ ~ +70℃ industrial wide temperature range

  8. Circuit Protection: Independent 6A SB channel fuses, short-circuit protection

  9. Limitation: Non-conformal coated PCB, redundancy function not supported

  10. Certification: CE industrial safety certified

4. Industrial Application Scenarios

  1. Chemical Industry: Solenoid valve on-off control, safety interlock actuator driving

  2. Power Industry: Auxiliary pump & fan relay control, boiler alarm light output

  3. Oil & Gas Industry: Emergency shut-off valve logic signal output

  4. General Process Control: Production line sequence interlock, equipment fault alarm driving