PR6423/003-030
Description
I. Model Explanation
PR6423: Φ8mm Standard Eddy Current Sensor Series
003: Armored Cable, Length 5 meters
030: Standard Sensitivity, Standard Linear Calibration Version
II. Basic Specifications
Probe Specifications: Diameter 8mm, Threaded Installation
Structure: Integrated Armored Shielded Cable, Resistant to Mechanical Tension, Resistant to Electromagnetic Interference
Adapter Compatibility: CON021 Special Matching
III. Measurement Performance Parameters
Standard linear range: 0 - 1.5mm
Rated sensitivity: 12 V/mm
Recommended gap for installation: 2.5mm
Matching midpoint voltage (with CON021): -12V
Frequency response: 0 - 12kHz
DC resistance of the coil: 4 - 6Ω
Insulation resistance: > 100MΩ
IV. Environmental Conditions
Probe operating temperature: -35℃ ~ +150℃
Cable operating temperature: -30℃ ~ +100℃
Protection level: IP67
Suitable for measured materials: 42CrMo4 ferromagnetic alloy steel, with surface roughness Ra ≤ 3.2μm
V. Compatibility and Usage
Must be paired: PR6423/003-030 + CON021
Application scenarios: Steam turbines, compressors, fans, shaft vibration, shaft displacement, phase comparison measurement
Compatible systems: MMS6000, AMS6500 TSI system
VI. Installation and Debugging Key Points
Standard installation gap: 2.5mm. After adjustment, the output of the preamplifier should be stable at -12V.
Shielded cables should be routed away from power cables and frequency converters to avoid parallel or co-located laying.
Single-ended grounding of the shielding layer, only grounding on the side of the preamplifier cabinet, and leaving the probe end floating.
The probe should be perpendicular to the measured shaft surface, avoiding the shaft edge to prevent edge effect.
VII. Normal Voltage Reference (with CON021 -24VDC power supply)
Gap is too small: Output approaches -4V
Standard operating point: 2.5mm → -12V
Gap is too large: Output approaches -20V
No voltage / Close to 0V: Probe disconnection, LEMO connector loosening, abnormal power supply