CIMR-XCBA20P4
Description
1. Basic Model Definition & Information
Model Code Breakdown: CIMR-XCBA20P4
CIMR = Yaskawa standard inverter prefix
XCB = VS Mini XCB advanced compact series
A = advanced function version
2 = 3‑Phase 200V input voltage class (AC200~230V)
0P4 = Rated applicable motor power: 0.4kW (0.5HP)
Typical Applications: Small conveyors, mini fans/pumps, packaging equipment, small automation machine spindle, lab drive system
2. Electrical Rating Parameters
Input Specification
3‑Phase Output Specification
Rated applicable motor: 0.4kW / 0.5HP
Inverter rated capacity: 1.1kVA, rated output current: 3A
Output voltage: 0 ~ AC230V 3-phase
Output frequency range: 0.5Hz ~ 400Hz
Control Mode: Sinusoidal PWM V/F open-loop control, low-noise carrier design
Overload Rating
3. Control I/O Configuration
Digital Input: 4-channel isolated 24VDC DI for FWD/REV run, multi-speed selection, fault reset
Analog Input: Dual configurable 0~10VDC / 4~20mA analog speed command input
Digital Output: 1 open-collector transistor DO + 1 SPST relay output for run status & fault alarm feedback
No built-in brake transistor, external dynamic braking resistor not supported for this model
Built-in basic PID function for closed-loop flow/pressure regulation; up to 16 preset multi-speed settings
4. Mechanical & Environmental Data
Mounting: Standard 35mm DIN rail or wall-mounted installation; Protection Grade: IP20
Overall dimension: W75 × H133 × D102mm, self-cooled natural convection cooling
Operating ambient temperature: -10℃ ~ +50℃ (no power derating within range); storage: -20℃ ~ +60℃
Ambient humidity: 5%~95%RH non-condensing, no corrosive gas or conductive dust
Net weight: Approx 0.75kg
Production Status: Original production discontinued; only surplus new or refurbished spare available for old equipment maintenance
5. Protection & Core Functions
Complete protection list: OC(Overcurrent), OV(Overvoltage), UV(Undervoltage), heatsink overheat, motor electronic thermal overload, output short-circuit & earth fault protection
Adjustable acceleration/deceleration: 0.1~600s; DC injection braking for quick motor stop
Low-frequency torque boost, auto energy-saving control for light-load energy reduction
Optional external digital operator for parameter setting, real-time frequency readout and fault code diagnosis
Get a Quote