ABB 3BHB005243R0105(KUC755 AE105) gate unit dedicated power supply module(GUSP)
June 04, 2026

ABB 3BHB005243R0105(KUC755 AE105) gate unit dedicated power supply module(GUSP)

This product is gate unit dedicated power supply module(GUSP) for ABB ACS6000 medium voltage high-power converter system, produced according to ABB internal industrial specification and IEC certification standard. It is matched with IGCT gate driver boards such as 3BHB004791R0101 to constitute complete power drive unit inside power cabinet. R0105 is optimized hardware revision with improved isolation circuit and anti-surge design, specially designed to output multi-channel isolated stabilized DC power required by IGCT drive control board, and realize real-time power state monitoring and fault feedback for peripheral drive components.

Description

1.Product Brief Introduction

This product is gate unit dedicated power supply module(GUSP) for ABB ACS6000 medium voltage high-power converter system, produced according to ABB internal industrial specification and IEC certification standard. It is matched with IGCT gate driver boards such as 3BHB004791R0101 to constitute complete power drive unit inside power cabinet. R0105 is optimized hardware revision with improved isolation circuit and anti-surge design, specially designed to output multi-channel isolated stabilized DC power required by IGCT drive control board, and realize real-time power state monitoring and fault feedback for peripheral drive components.

2.Model Definition Explanation

3BHB is fixed part prefix of ABB medium voltage converter IGCT auxiliary power and drive PCB series.
005243 stands for exclusive factory development serial number of this gate power module.
R0105 represents upgraded fifth revision hardware version with optimized component layout, isolation performance and built-in protection circuit.
KUC755 AE105 is the ABB internal type code of this power supply module.

3.Technical Specifications

Rated input voltage is 200~240VAC single-phase alternating current, input allowable fluctuation range ±10%. It outputs multiple groups of isolated stabilized DC including +5VDC, ±15VDC and +24VDC for matched IGCT drive boards, maximum total output rated current is 5A, overall power conversion efficiency above 90%. Working ambient temperature ranges from 0℃ to +65℃, storage temperature from -40℃ to +85℃ under non-condensing humidity environment. It adopts cabinet built-in installation with IP20 protection grade, passes IEC61000 EMC anti-interference and industrial anti-vibration certification, equipped with built-in overvoltage, overcurrent, short-circuit and overtemperature four-level automatic protection circuit.

4.Interface and Communication Configuration

One group of AC input terminal is used for connecting cabinet auxiliary AC power source. Multi-group pin-type DC output terminals are directly wired to matching IGCT gate drive control board for power supply transmission. Internal optical fiber interface transmits power module running status and fault alarm signal to upper master control unit. No independent external Ethernet or serial communication port is equipped, all fault and status data are transmitted through converter internal proprietary optical bus protocol.

5.Core Functions

It converts input alternating current into multiple groups of isolated low-voltage stabilized direct current to provide reliable working power for IGCT gate drive circuit board. It continuously samples output voltage and current in real time, automatically cuts off output once overvoltage, overload or short-circuit fault occurs to avoid damage to rear-end drive board and IGCT power device. It uploads fault code via optical fiber to main control system to trigger unit interlock stop and system fault alarm. Built-in surge absorption circuit restrains instantaneous high voltage impulse interference generated during power device switching.

6.Application Scenarios

It is installed inside INU power unit cabinet of ABB ACS6000 medium voltage frequency converter system. Widely used for high-power speed regulation of large induced draft fan and circulating water pump in thermal power plant, main transmission driving of metallurgical rolling mill production line, rotary kiln drive of cement plant, heavy-duty belt conveyor control of mine and large compressor variable frequency system of chemical industry, also applicable for excitation cabinet power supply of power station generator set.

7.Operation and Maintenance Instructions

Cut off cabinet main power and auxiliary AC power completely before disassembly or replacement, keep power-off for more than 30 minutes to fully discharge residual capacitance voltage inside module. Fix module on specified mounting slot evenly and tighten fixing screws, connect input and output wiring strictly following official terminal definition to prevent reverse connection and short-circuit damage. Implement regular maintenance every six months, clean surface dust and terminal dirt with dry soft brush, forbid liquid cleaning agent contact with circuit components. Replace whole module when continuous power output failure or recurring protection shutdown appears after excluding peripheral wiring and rear-end drive board faults, unauthorized disassembly and internal circuit modification are strictly prohibited.


Get a Quote