ABB 1TNE968901R4300 official TA562-RS expansion accessory tailored
June 04, 2026

ABB 1TNE968901R4300 official TA562-RS expansion accessory tailored

This component is an official TA562-RS expansion accessory tailored for ABB AC500, AC500-eCo and AC500-S series PLC systems under the 1TNE component coding system. It is a plug-in RS485 communication expansion board manufactured in compliance with CE, UL and RoHS standards as well as ABB global production specifications. The compact circuit structure can be directly inserted into the dedicated expansion slot of PLC CPU to add an independent RS485 communication channel without occupying the original built-in serial port resource of the main controller, which optimizes communication layout and improves external device access capability of the whole control system.

Description

1.Product Brief Introduction

This component is an official TA562-RS expansion accessory tailored for ABB AC500, AC500-eCo and AC500-S series PLC systems under the 1TNE component coding system. It is a plug-in RS485 communication expansion board manufactured in compliance with CE, UL and RoHS standards as well as ABB global production specifications. The compact circuit structure can be directly inserted into the dedicated expansion slot of PLC CPU to add an independent RS485 communication channel without occupying the original built-in serial port resource of the main controller, which optimizes communication layout and improves external device access capability of the whole control system.

2.Model Definition Explanation

1TNE is the unified general prefix of ABB low voltage automation spare parts for global ordering and product classification management.
9689 is internal catalog grouping code standing for AC500 PLC matched accessory product range.
01 represents fixed base structural version of the accessory framework.
R means factory pre-assembled standard finished configuration following ABB internal component coding regulations.
4300 is exclusive configuration serial number corresponding to TA562-RS, specially defined as screw terminal RS485 expansion card and distinguished from power terminal modules and RTC accessory variants.

3.Technical Specifications

The module obtains working power supply directly through CPU internal backplane bus with no extra external DC power required. Rated applicable bus voltage is DC24V supplied by matched PLC host. Rated working ambient temperature ranges from -25℃ to +60℃, storage temperature covers -40℃ to +85℃. The RS485 interface supports maximum baud rate up to 115200bps and the maximum effective transmission distance reaches 1200 meters under low-speed communication condition. The whole product is IP20 protection grade for cabinet inner installation and passes IEC61000 EMC anti-interference and industrial vibration certification. Each screw terminal can withstand rated voltage up to 250VAC.

4.Interface and Communication Configuration

Three-position screw wiring terminals are arranged on the front for A line, B line and grounding connection of RS485 bus to link field instruments, inverters and distributed I/O equipment. Gold finger docking structure on the rear side enables plug-in connection with CPU dedicated expansion slot to complete internal data interaction via PLC backplane bus. Built-in hardware circuit supports Modbus RTU master and slave communication mode. No embedded Ethernet or Profibus circuit is reserved on this board and independent DIN rail installation structure is not available as the module is designed for embedded installation inside CPU housing.

5.Core Functions

Its core function is to expand one independent hardware RS485 communication channel for AC500 series PLC. It separates newly expanded communication port from original onboard serial interface to build independent communication links for different groups of field devices. Relying on Modbus RTU protocol, it realizes real-time data exchange between PLC and peripheral frequency converters, sensors, transmitters and remote I/O modules. It avoids communication congestion and resource conflict caused by multi-device access on a single original serial port and enhances communication stability and system expansion flexibility of the automation control system.

6.Application Scenarios

It is widely matched with AC500 series PLC in medium and small automation projects including packaging machine control, water treatment automatic control, centralized control of pumps and fans, food production line and textile machinery control cabinets. It is also commonly equipped in intelligent building power distribution control, environmental monitoring system and small logistics conveying equipment control, responsible for accessing various RS485-type field site equipment.

7.Operation and Maintenance Instructions

Cut off the total power supply of matched PLC CPU before installation and insert the expansion card vertically into the designated slot until mechanical locking is finished. Complete field bus wiring strictly according to terminal polarity definition of A, B and GND and configure terminal matching resistor at the tail end of communication bus based on actual field cable length. Perform routine maintenance inspection every six months and remove accumulated dust on circuit board and terminals with dry soft brush while forbidding liquid cleaning solvent. Replace the whole expansion board immediately in case of continuous communication breakdown, terminal burning or abnormal overheating during equipment operation and unauthorized disassembly or modification of internal circuit components is prohibited.