Product Introduction MC-PAIH03 is a high-level analog input IOP processing card of the Honeywell PMIO series. It is compatible with the I/O rack of the Experion PKS C200/C300 controller. It collects standard analog signals of two-wire transmitters from the field, including voltage and current. It has built-in onboard computing capabilities, performing AD conversion, engineering quantity conversion, and alarm judgment. It is a mainstream and conventional AI acquisition card for refineries and power plants.

Description

Model Explanation

MC = PMIO series I/O module; PAIH = High Level Analog Input; 03 = Hardware version; Overall equipment material code 51304754-150. Technical Specifications

Channel: 16 differential isolated analog input channels

Supported signals: 4-20mA (with base 250Ω sampling), 1-5V, 0-5V, 0.4-2V DC voltage

Sampling rate: Single channel 4 times/second, all 16 channels complete one round of inspection in 250ms

Measurement accuracy: Normal temperature 23℃ ± 2℃ ≤ ±0.075% FS; 0-50℃ full temperature range ≤ ±0.15% FS

Input impedance: Voltage input > 10MΩ, channel withstand voltage ±30V surge protection

Crosstalk suppression: DC-60Hz crosstalk attenuation between channels 60dB, 60Hz AC common mode suppression 32dB

Power consumption: Backplane 24V rack power supply, net weight approximately 0.6kg

Environment: -20℃ to +60℃, humidity 5% to 95% no condensation, CE industrial certification

Interface and communication configuration

Panel: Power, operation, fault status LED indicators;

Backplane: European style gold finger plug-in PMIO rack, I/O Link bus and C200/C300 main control for data interaction;

Field wiring:配套 FTA terminal base (MU-TAIH02/TAIH12 series), field instrument cables connected to the terminal of the base, cards connect to the base through jumper wires;

System architecture: Supports redundant rack configuration, module data uploaded to the FTE network to the upper HMI via the controller.

Core functions

16-channel independent differential acquisition, hardware RC first-order filtering (-3dB@1Hz) to suppress on-site interference; Built-in polynomial engineering quantity conversion, can directly configure temperature and pressure compensation linear algorithm; Full-channel open circuit, short circuit, over-range hardware self-diagnosis, fault codes uploaded to the control system; Single-channel fault does not affect other circuits' acquisition; Modules support hot-swappable power-on of the rack, replacement spare parts automatically download configuration parameters. Applicable scenarios

Temperature / pressure / level transmitters for petrochemical plants, monitoring of auxiliary parameters for thermal power boilers, collection of parameters for continuous production processes in coal chemical industry, DCS analog quantity collection for pharmaceuticals / water treatment.

Installation and Maintenance Instructions

Field instruments use shielded twisted-pair cables, with the shielding layer grounded at a single point in the cabinet; for 4-20mA circuits, strictly select the matching FTA base with a precise 250Ω resistor; conduct annual inspection of channel accuracy; for damp cabinets, take measures to prevent terminal moisture;严禁 unplugging or plugging connectors and connecting lines between the card and the base while the equipment is powered on.