Honeywell 8C-PCNT01 (Series 8 High-Speed Pulse Counting Module, C300 DCS System)
June 03, 2026

Honeywell 8C-PCNT01 (Series 8 High-Speed Pulse Counting Module, C300 DCS System)

Product Introduction 8C-PCNT01 is a 8-channel high-speed pulse counting module specifically designed for the Honeywell Experion PKS Series8 series. It is used in conjunction with the C300 controller rack and is dedicated to collecting pulse and frequency signals output by flow meters, encoders, and speed sensors. It is used for cumulative measurement, speed calculation, and displacement counting. It is a dedicated I/O card for trade settlement, unit speed measurement, and high-precision quantitative batching.

Description

Model Interpretation

8C = Series8 I/O module; PCNT = Pulse Counter; 01 = Initial standard 8-channel hardware version. Technical Specifications

Power Supply: 24VDC power supply on the backplane of the rack, with the overall power consumption approximately 2W

Channels: 8 independent pulse input channels, with the maximum input frequency of each channel up to 1MHz

Input Signals: NPN/PNP passive contacts, 5V/24V level pulses, encoder A/B phase quadrature pulses

Measurement Accuracy: Pulse counting ±1 pulse error, frequency measurement accuracy 0.01% FS

Operating Environment: -20℃ to +60℃, relative humidity 5% to 95% without condensation; CE and UL explosion-proof certifications, suitable for chemical explosion-proof areas

Dimensions: 144×108×50mm, net weight approximately 0.32kg

Interface and Communication Configuration

Panel: LED indicators for power, operation, fault, and channel status;

Backplane: Gold finger plug-in for C300 rack bus, data interaction through I/O Link bus and CC-PCNT controller;

Field Wiring: Equipped with dedicated IOTA terminal base, 8-channel pulse signal lines are separately connected to the terminal of the base;

System Communication: Data is uploaded to the C300 main control via the backplane, relying on FTE Ethernet and the upper HMI to exchange measurement data.

Core Functions

8-channel independent pulse accumulation, instantaneous frequency conversion, supports one-way counting, A/B phase bidirectional increment/decrement counting;

Hardware filtering to suppress interference from on-site cables and contact jitter, avoiding pulse miscounting;

Software setting of count upper limit alarm, automatically triggering interlock signal upon reaching the set value;

Channel disconnection, short circuit self-diagnosis, fault location displayed in the pop-up window of the upper system;

Support for flow accumulation, real-time speed conversion, displacement length conversion, suitable for trade measurement and settlement logic. Applicable scenarios

Refining / Chemical Raw Materials Trading Flow Meter Measurement, Power Plant Fan / Turbine Speed Monitoring, Coal Chemical Quantitative Loading Control System, Water Plant Flow Meter Cumulative Statistics, Metallurgical Production Line Encoder Position Acquisition.

Operation and Maintenance Instructions

For on-site pulse cables, use shielded twisted pair cables, with the shielded layer grounded at one end of the cabinet;

Modules support hot-swappable power-on insertion, and after replacing spare parts, the system will automatically download parameters, without the need for reconfiguration;

Regularly check the wiring of the terminal base to ensure it is tightened; for humid conditions, take measures to prevent the terminals from getting damp;

Module parameters are configured in the Experion configuration software for counting mode, range, and alarm threshold.