Honeywell CC-PAOX01 & CC-PCF901 (C300 Experion PKS C-Series Module)
CC-PAOX01
Product Introduction
CC-PAOX01 is Honeywell C-series 16CH HART analog output module for C300 PKS DCS, outputs 4–20mA regulating signal to field control valve & HART smart positioner, mates with dedicated TAOX type IOTA terminal base.
Description
Model Interpretation
CC=C300 C-series I/O; PAOX=Process Analog Output HART version; 01=16-channel standard specification.
Technical Specifications
Power: 24VDC backplane feed, typical power consumption 4.9WChannels: 16-channel 4–20mA AO, HART7 compliant; max loop load 750ΩPrecision: ±0.05%FS output accuracy; channel-backplane isolation 1500VACAmbient: -40℃~+70℃, 5%~95%RH non-condensing; UL/CE, Class I Div.2 certified
Interface and Communication Configuration
Front: Power/Run/Fault/HART four LED indicators; rear gold finger connects CC-TAOX01(non-redundant) / CC-TAOX11(redundant) IOTA base; HART signal superimposed on analog field cable.
Core Function
Convert CPU digital command into 4–20mA analog signal to adjust field regulating valve opening.
Realize remote HART reading for valve stroke, fault code and online instrument calibration.
Independent per-channel short/open detection, configurable fail-safe output preset via software.
Applicable Scenarios
Petrochemical refining regulation cabinet, chemical reactor control rack, power plant boiler feedwater control cabinet.
Operation and Maintenance Instructions
Shielded twisted-pair field cable with single-point ground; hot-swappable, auto-load configuration after spare replacement.
CC-PCF901
Product Introduction
CC-PCF901 is C300 Process Control Firewall module, network safety isolation card separating control FTE network and upper supervisory network to block illegal network access.
Model Interpretation
CC=C300 accessory module; PCF=Process Control Firewall; 901=standard single firewall specification.
Technical Specifications
Power: Backplane 24VDC, typical 2.7W consumptionCommunication: Dual independent 10/100Mbps FTE RJ45 ports, IP/TCP/UDP packet filtering functionAmbient: -20℃~+60℃ operating temperature; CE/UL certification, fits Experion R410+ system
Interface and Communication Configuration
Front LED: Power/Run/Link/Alarm status lamps; rear backplane gold finger to C300 rack bus; two external FTE Ethernet ports for control net & monitor net wiring separately.
Core Function
Hardware firewall filtering, isolate supervisory network abnormal broadcast storm to protect real-time control network.
Access whitelist configuration, forbid unauthorized IP accessing controller resource; record network abnormal log and upload alarm to HMI.
Applicable Scenarios
Main control rack of thermal power / refining / coal chemical central control room DCS system.
Operation and Maintenance Instructions
Install between controller slot and upper switch; industrial shielded FTE cable required; hot plug available, firewall rules edited via Experion software.