Honeywell CC-PAIX01 & CC-PAOH01 (C300 Experion PKS C-Series I/O Module)
Description
Model Interpretation
CC = C300 C-series I/O code; PAIX = Process Analog Input for Thermocouple/RTD Mixed; 01 = 16-channel standard specification.
Technical Specifications
Power supply: 24VDC fed from backplane, typical power consumption 4.4W
Channel allocation: 16 single-ended / 8 differential configurable; supports TC(B/E/J/K/T/S/R/N) + PT100/PT1000 RTD + 4–20mA analog signal
Conversion precision: 22-bit ADC, accuracy ±0.075%FS; channel-to-backplane isolation 1500VAC
Ambient: -40℃ ~ +70℃ working temp, 5%~95%RH non-condensing; UL/CE, Class I Div.2 certification
Interface and Communication Configuration
Front panel: Power, Run, Fault status LED indicators; rear gold finger plugged onto corresponding IOTA base, all field thermal element wiring terminated on IOTA terminal block, no HART bus.
Core Function
Collect furnace, pipeline, equipment temperature via thermocouple/RTD and convert into digital value for C300 control logic.
Automatic open-circuit detection for broken thermal wire and over-range alarm, fault message uploaded to Experion HMI.
Flexible channel type configuration via DCS software without hardware change.
Applicable Scenarios
Thermal power boiler, petrochemical reactor, chemical furnace temperature measurement cabinet with large amount of thermal sensors.
Operation and Maintenance Instructions
Install on dedicated C300 IOTA base; thermal cable uses special compensating wire; module supports hot swap; new spare card auto-load configuration after power on.
CC-PAOH01
Product Introduction
CC-PAOH01 is Honeywell C-series 16-channel HART analog output module for C300 PKS system, outputs 4–20mA control signal to field positioning valve, actuator and smart positioner with HART digital communication function.
Model Interpretation
CC = C300 I/O series; PAOH = Process Analog Output with HART; 01 = 16-channel standard specification.
Technical Specifications
Power: Backplane 24VDC supply, typical power consumption 4.7W
Channels:16-channel 4–20mA analog output, HART7 compatible
Output precision: ±0.05%FS full scale; channel-backplane isolation 1500VAC
Working range: -40℃ ~ +70℃; UL/CE, ATEX Zone2 & Class I Div.2 approval
Interface and Communication Configuration
Front LED: Power, Healthy, HART status indicators; rear connects matched IOTA terminal base, all field control wiring wired on IOTA terminals; HART signal multiplexed on analog output loop.
Core Function
Receive control instruction from C300 CPU, convert digital command into 4–20mA analog signal to regulate field control valve opening.
HART communication enables remote reading of smart valve feedback, stroke fault and online parameter calibration of valve positioner.
Output short-circuit protection per channel to avoid internal circuit damage caused by field wiring failure.
Applicable Scenarios
Refining unit regulating loop cabinet, chemical continuous process valve control rack, power plant boiler feed water/steam regulation system.
Operation and Maintenance Instructions
Field control cable uses shielded twisted pair with single-point grounding; hot-plug replaceable online; no program download required after spare replacement.
Get a Quote