Honeywell CC-PAIM01 & CC-PAIN01 (Experion PKS C300 C-Series Analog Input Modules)
Description
Model Interpretation
CC=C300 C-series I/O family; PAIM=Process Analog Input Multi-range; 01=standard 16-channel specification code.
Technical Specifications
Power: 24VDC via backplane, typical power consumption 4.3W
Channel: 16 configurable single-ended /8 differential input; support 4–20mA,1–5VDC, RTD, TC thermocouple signals
Accuracy: 22-bit AD conversion, ±0.075%FS precision; channel-backplane isolation 1500VAC
Ambient: Operating -40℃~+70℃, RH5%~95% non-condensing; UL/CE, Class I Div.2 certification
Interface and Communication Configuration
Front panel LED indicators: Power, Run, Fault; rear gold finger connected to IOTA base, all field sensor wiring terminated on IOTA terminal block, no HART communication port.
Core Function
Collect temperature (RTD/TC), pressure, flow conventional analog signals and convert to digital value for C300 controller PID calculation.
Auto detect open-circuit, over-range for field loop and upload fault alarm to Experion HMI.
Multi-type signal flexible configuration via system software without hardware modification.
Applicable Scenarios
Thermal power plant boiler, conventional chemical workshop non-smart instrument cabinet, site with ordinary passive transmitters and thermal elements.
Operation and Maintenance Instructions
Mount on standard C300 IOTA base; hot swappable during system live running; spare module automatically loads configuration after power-on without offline programming.
CC-PAIN01
Product Introduction
CC-PAIN01 is Honeywell C300 high-precision isolated non-HART analog input module, 8-channel per-channel galvanic isolation design for strong EMI industrial environment, no built-in HART protocol.
Model Interpretation
CC=C300 I/O series; PAIN=Process Analog Input Isolated; 01=8 full isolated channel version.
Technical Specifications
Power: Backplane 24VDC supply, typical 4.8W power consumption
Channel:8 fully galvanic isolated input, signal range 4–20mA /1–5VDC
Isolation: Per-channel 2500VAC isolation to eliminate ground loop interference
Operating Temp:-40~+70℃; CE/UL, ATEX Zone2 approved
Interface and Communication Configuration
Front status LED: Power, Healthy, Channel Alarm; rear docking exclusive IOTA terminal base for field wiring connection.
Core Function
Anti-interference analog signal sampling for field with large motor, inverter layout, prevent signal drift caused by ground potential difference.
Independent channel fault diagnosis for wire break and overload, real-time fault reporting to DCS control system.
Applicable Scenarios
Metallurgy, coal chemical, waste gas recovery high-electromagnetic interference control cabinet.
Operation and Maintenance Instructions
Use shielded twisted-pair field cable with single-end shield grounding; support hot replacement, no parameter download needed after spare installation.