JANCD-TU05REV.C0
Description
1. General Information
2. Specifications
2.1 Electrical
Supply Voltage: 24 VDC ±10%
Fuses: 2 × 5 A fast-blow fuses
Relay Rating: 24 VDC / 5 A (resistive load)
Control Functions: Main contactor drive, E-stop safety interlock, auxiliary power distribution
2.2 Physical
Dimensions: 120 mm × 100 mm × 30 mm
Weight: Approx. 100 g
Mounting: Standard slot in XRC/ERC cabinet; 4 × M3 screws (torque: 0.8–1.0 N·m)
2.3 Environmental
Operating Temperature: 0 °C to +40 °C
Storage Temperature: −10 °C to +60 °C
Humidity: 5%–80% RH, non-condensing
Vibration: ≤ 0.5 G (10–500 Hz)
Altitude: ≤ 1,000 m above sea level
2.4 Compatibility
Replaces: JANCD-TU05 REV.A / REV.B (fully backward compatible, no wiring changes needed)
Applications: Welding, material handling, assembly, general automation
3. Interface & Connectors
CN1: 24 VDC power + control signal input (from CPU/safety circuit)
CN2: Main contactor coil output
CN3: Emergency stop / safety interlock input
CN4: Auxiliary power distribution output
4. LED Indicators
PWR (Green): ON when 24 VDC supply is normal
ON (Green): ON when main contactor is energized (closed)
ALM (Red): ON for fuse blow, E-stop circuit open, or relay coil fault
5. Installation Instructions
Power OFF the controller; wait 5 minutes for internal capacitors to discharge.
Wear an anti-static wristband to prevent ESD damage.
Insert the board into the designated cabinet slot; secure with 4 × M3 screws.
Connect CN1–CN4 per the cabinet wiring diagram.
Power ON the controller; verify: PWR = ON, ON = ON, ALM = OFF.
6. Safety & Protection Features
Dual 5 A fuses: Overcurrent protection for control circuits
E-stop interlock: Complies with Safety Category 3
Relay isolation: Electrical separation between low-voltage control and power circuits
Fault alarm: ALM signal sent to controller for diagnostic logging
7. Maintenance & Troubleshooting
7.1 Maintenance Schedule
Quarterly: Check connector tightness and fuse condition.
Annually: Clean dust with low-pressure dry air; inspect relay contacts for wear.
7.2 Troubleshooting
PWR OFF: Check 24 VDC supply and CN1 wiring.
ALM ON: Check 5 A fuses, E-stop circuit continuity, and relay coil.
ON OFF (PWR ON): Check main contactor coil and CN2 connections.
Intermittent operation: Inspect connector pins and relay contacts for corrosion.
8. Ordering & Warranty
Part Number: JANCD-TU05 REV.C0
Origin: Japan
Warranty: 12 months under normal operating conditions
9. Warnings
For qualified technical personnel only.
Disconnect all power sources before servicing; wait for capacitor discharge.
Do not modify the board or replace fuses with incorrect ratings (risk of fire or equipment damage).
Yaskawa is not liable for improper use, modification, or installation.