SR369-HI-R-M-0-P-0-E (GE Multilin 369 Motor Management Relay)
Description
Model Interpretation
SR369: 369 series motor management relay
HI: High‑impedance control power (60–265 VAC / 50–300 VDC, 48–62 Hz)
R: 12 built‑in 3‑wire RTD inputs (Pt100, Ni100/120, Cu10)
M: Enhanced metering package (3‑phase, power, energy, demand)
0: No fiber‑optic port
P: Profibus‑DP communication interface
0: No harsh environment conformal coating
E: Enhanced diagnostics + 40‑character LCD front panel
Technical Parameters
Input & Power
CT Input: 5 A secondary phase current (standard); 1 A optional
VT Input: 60–120 V phase‑neutral
Control Power: 60–265 VAC / 50–300 VDC, 48–62 Hz
Power Consumption: ≤10 VA typical
Protection Functions
Thermal: Overload (thermal memory), RTD‑based winding/bearing overtemperature
Electrical: Phase/ground overcurrent, unbalance, loss of load, reverse power, stall/locked rotor
Voltage/Frequency: Over/undervoltage, over/underfrequency, single‑phase protection
Mechanical: Vibration monitoring (analog inputs), start‑up failure detection
Trip Time: ≤200 ms (differential); ≤15 ms (instantaneous overcurrent)
I/O & Interfaces
RTD Inputs: 12 × 3‑wire (Pt100, Ni100/120, Cu10)
Analog Outputs: 4 × 4–20 mA, isolated
Digital Inputs: 16 opto‑isolated (dry/wet contact, ≤1 ms response)
Relay Outputs: 8 Form C (5 A / 250 VAC)
Communication: RS‑232 (front, programming), RS‑485 (Modbus RTU), Profibus‑DP (P option)
Display & User Interface
Display: 40‑character backlit LCD (enhanced)
Indicators: 12 LED (RUN, TRIP, ALARM, FAULT, SERVICE)
Keypad: Numeric/navigation for local programming; help key
Mechanical & Environmental
Dimensions: 296 mm H × 107 mm W × 205 mm D
Mounting: Panel mount (19” rack compatible)
Enclosure: Flame‑retardant plastic; IP50 (front), IP20 (overall)
Operating Temp: -40°C to +60°C
Storage Temp: -40°C to +85°C
Humidity: 5–95% non‑condensing
Certifications: UL, CE, CSA, IEC 60255, ATEX
Metering & Diagnostics
Metering: 3‑phase current/voltage, power, energy, frequency, PF, demand (0.5% accuracy)
Diagnostics: Event log (512 events), fault recorder (128‑cycle oscillography), pre‑trip data
Thermal Modeling: RTD biasing, load loss cooling curves, hot‑spot estimation
Motor Health Report: Graphical diagnostics for maintenance planning
Core Functions
Comprehensive Motor Protection: Guards against electrical faults, thermal overload, and mechanical issues (stall, vibration).
Precision Thermal Monitoring: 12 RTD inputs for winding/bearing temperature tracking and hot‑spot prediction.
High‑Voltage Compatibility: Wide‑range HI power for flexible substation integration.
Advanced Communications: Profibus‑DP + Modbus RTU for SCADA and DCS integration.
Enhanced Diagnostics: Oscillography, event logging, and motor health reports for root‑cause analysis.
Auto‑Configuration: Motor Settings Auto‑Configurator simplifies setup.
Applications
Industrial Motors: Medium‑to‑large three‑phase AC motors (LV/MV)
Oil & Gas: Pumps, compressors, fans, down‑hole pumps
Water Treatment: Blowers, mixers, high‑power pumps
Metallurgy: Rolling mills, conveyors, furnace motors
HVAC: Large chiller motors, air handlers
Mining: Conveyors, crushers, hoists
Usage & Maintenance
Installation: Panel‑mount; wire CT/VT, HI control power, RTDs, and communications.
Programming: Use front keypad or connect to EnerVista 369 software via RS‑232.
Configuration: Set CT/VT ratios, protection curves, RTD types, and I/O mapping.
Maintenance: Inspect terminals annually; update firmware; verify settings after system changes.
Note: 369 series is discontinued; replacement is GE Multilin 859 series.
Get a Quote