SR745-W2-P5-G5-HI (GE Multilin 745 Transformer Protection Relay)
Description
Model Interpretation
SR745: 745 series transformer protection relay
W2: 2‑winding transformer configuration
P5: 5 A CT secondary phase current input
G5: 5 A ground CT input
HI: High‑impedance control power (70–265 VAC / 90–300 VDC, 48–62 Hz)
Technical Parameters
Input & Power
CT Input: 5 A phase (2 windings); 5 A ground
VT Input: 60–120 V phase‑neutral
Control Power: 70–265 VAC / 90–300 VDC, 48–62 Hz
Power Consumption: ≤12 VA typical
Protection Functions
Differential: 2‑winding restrained differential, high‑speed (≤8 ms trip)
Overcurrent: Phase/ground, IEC inverse/definite time, 0.1–20×In
Thermal: Winding/iron core overload, RTD‑based overtemperature
Voltage/Frequency: Over/undervoltage, over/underfrequency, overexcitation blocking
Ground Fault: Restricted earth fault (REF), high‑Z ground fault
Trip Time: ≤8 ms (differential); ≤15 ms (overcurrent)
I/O & Interfaces
Analog Inputs: 4 RTD (3‑wire; Pt100, Ni100/120, Cu10)
Analog Outputs: 4 × 4–20 mA, isolated, 600 Ω burden max
Digital Inputs: 16 opto‑isolated (dry/wet, ≤1 ms)
Relay Outputs: 8 Form C (5 A / 250 VAC)
Communication: RS‑232 (front), RS‑485 (Modbus RTU), Ethernet (IEC 61850, DNP3)
Display & User Interface
Display: 40‑character backlit LCD
Indicators: 12 LED (RUN, TRIP, ALARM, FAULT, SERVICE)
Keypad: Numeric/navigation for local programming
Mechanical & Environmental
Dimensions: 228.6 mm H × 177.8 mm W × 180.9 mm D (9”×7”×7.125”)
Mounting: Panel mount (19” rack compatible)
Enclosure: Flame‑retardant plastic; IP50 (front), IP20 (overall)
Operating Temp: -40°C to +60°C
Storage Temp: -40°C to +85°C
Humidity: 5–95% non‑condensing
Certifications: UL, CE, CSA, IEC 60255, ATEX
Metering & Diagnostics
Metering: 3‑phase current/voltage, power, energy, frequency, PF, demand (0.2% accuracy)
Diagnostics: Event log (1024 events), fault recorder (256‑cycle oscillography), pre‑trip data
Thermal Modeling: RTD biasing, load loss cooling curves, hot‑spot estimation
Core Functions
High‑Speed Differential Protection: Detects internal winding faults in <10 ms to prevent catastrophic failure.
Comprehensive Thermal Protection: Monitors winding/bearing temps via RTDs and models thermal stress.
Wide‑Range HI Power: Operates from 70–265 VAC / 90–300 VDC for flexible substation integration.
Advanced Communications: Ethernet IEC 61850 for grid‑wide SCADA and Modbus for legacy systems.
Robust Fault Diagnostics: Captures oscillography and event logs for root‑cause analysis.
Applications
Power Utilities: Transmission/distribution transformers, substations
Oil & Gas: Step‑up/down transformers, offshore platforms
Metallurgy: Furnace transformers, heavy‑duty process units
Petrochemical: Refinery transformers, corrosive environments
Renewables: Wind/solar farm grid‑intertie transformers
Usage & Maintenance
Installation: Panel‑mount; wire CT/VT, HI control power, RTDs, and communications.
Programming: Use front keypad or connect to EnerVista 745 software via RS‑232/Ethernet.
Configuration: Set CT/VT ratios, differential slopes, protection curves, and RTD types.
Maintenance: Inspect terminals annually; update firmware; verify settings after system changes.