SR489-P5-LO-A20-E (GE Multilin 489 Generator Management Relay)
Description
Model Interpretation
SR489: 489 series generator management relay
P5: 5 A CT secondary phase current input
LO: Low‑voltage control power (20–60 VDC / 20–48 VAC, 48–62 Hz)
A20: 4 isolated 4–20 mA analog outputs
E: Enhanced front panel (40‑character LCD, no Ethernet)
Technical Parameters
Input & Power
CT Input: 5 A phase (5 channels); 2 ground CT inputs
VT Input: 0–690 V (delta/wye configurable)
Control Power: 20–60 VDC / 20–48 VAC, 48–62 Hz
Power Consumption: ≤8 VA typical
Protection Functions
Stator: Overload (thermal memory), phase overcurrent (voltage‑restrained), ground fault (100% stator earth), negative sequence overcurrent
Rotor: Loss of excitation, reverse power, over/undervoltage, over/underfrequency
Mechanical: Bearing overtemperature (12 RTD inputs), vibration monitoring (4 analog inputs)
Timing: IEC inverse / definite time curves; trip time ≤15 ms (instantaneous)
I/O & Interfaces
Analog Outputs: 4 × 4–20 mA, isolated
Digital Inputs: 9 opto‑isolated (dry/wet contact, ≤1 ms response)
Relay Outputs: 6 Form C (5 A / 250 VAC)
RTD Inputs: 12 × 3‑wire (100Ω Pt, 100/120Ω Ni, 10Ω Cu)
Communication: RS‑232 (front, programming), RS‑485 (Modbus RTU/DNP3.0); no Ethernet
Display & User Interface
Display: Enhanced 40‑character backlit LCD
Indicators: 10 LED status (RUN, TRIP, ALARM, FAULT, SERVICE)
Keypad: Numeric/navigation for local programming
Mechanical & Environmental
Dimensions: 177.5 mm H × 128.5 mm W × 119 mm D
Mounting: DIN rail or panel mount
Enclosure: Flame‑retardant plastic; IP50 (front), IP20 (overall)
Operating Temp: -40°C to +70°C
Storage Temp: -40°C to +85°C
Humidity: 5–95% non‑condensing
Certifications: UL, CE, CSA, IEC 60255
Metering & Diagnostics
Metering: 3‑phase current/voltage, power, energy, frequency, PF, demand (0.5% accuracy)
Diagnostics: Event log (512 events), fault recorder (128‑cycle oscillography), pre‑trip data
Thermal Modeling: RTD biasing, current unbalance biasing, cooling time constants
Core Functions
Comprehensive Generator Protection: Guards against stator/rotor electrical faults and mechanical issues (bearing overheating, vibration).
Precision Monitoring: Real‑time tracking of electrical parameters and winding/bearing temperatures via RTDs.
Low‑Voltage Compatibility: Wide‑range LO power for 24/48 VDC industrial systems.
Flexible Control: Configurable grid‑connection logic, protection curves, and fault responses.
SCADA Integration: Modbus RTU/DNP3.0 over RS‑485 for remote monitoring/control.
Enhanced Local Operation: Large LCD for clear diagnostics and on‑site programming.
Applications
Industrial Generators: Small‑to‑medium synchronous/induction generators (low‑voltage)
Power Plants: Auxiliary generators, co‑generation systems
Oil & Gas: Onshore generator sets, gas turbine units
Water Treatment: Biogas generators, backup power systems
Manufacturing: Emergency/standby generators, island‑mode operation
Usage & Maintenance
Installation: Mount on DIN rail/panel; wire CT/VT, LO control power, RTDs, and communications.
Programming: Use front keypad or connect to EnerVista 489 software via RS‑232.
Configuration: Set CT/VT ratios, protection curves, RTD types, and I/O mapping.
Maintenance: Inspect terminals annually; update firmware periodically; verify settings after system changes.
Get a Quote