SR469-P5-HI-A20-H (GE Multilin 469 Motor Management Relay)
June 02, 2026

SR469-P5-HI-A20-H (GE Multilin 469 Motor Management Relay)

Product Description The SR469-P5-HI-A20-H is a harsh-environment enhanced motor management relay from GE Multilin’s 469 series, designed for medium‑voltage motors in extreme industrial conditions. It adds conformal coating for corrosion and moisture resistance, alongside full protection, metering, and control capabilities.

Description

Model Interpretation

SR469: 469 series motor management relay (draw‑out modular platform)

P5: 5 A CT secondary phase current input

HI: High‑impedance wide‑range control power (70–265 VAC / 90–300 VDC)

A20: 4 isolated 4–20 mA analog outputs

H: Harsh environment (conformal coating; no Ethernet)

Technical Parameters

Input & Power

CT Input: 5 A phase (5 channels); 2 ground CT inputs

VT Input: 0–690 V (delta/wye configurable)

Control Power: 70–265 VAC / 90–300 VDC, 48–62 Hz

Power Consumption: ≤10 VA typical

Protection & Timing

Protection Functions: Overload (thermal memory), short circuit, ground fault (high‑Z), stall, undervoltage/overvoltage, phase loss/reversal, RTD overtemperature, mechanical jam, torque protection

Overcurrent Curves: IEC 60255‑3 inverse / definite time, 0.1–10×In

Trip Time: ≤10 ms (instantaneous); ±50 ms accuracy

I/O & Interfaces

Analog Outputs: 4 × 4–20 mA, isolated, burden >500 kΩ

Digital Inputs: 9 opto‑isolated (dry/wet contact, ≤1 ms response)

Relay Outputs: 6 Form C (5 A / 250 VAC)

RTD Inputs: 3‑wire; 100Ω Pt, 100/120Ω Ni, 10Ω Cu (stator thermal protection)

Communication: RS‑232 (front, programming), RS‑485 (Modbus RTU, half‑duplex); no Ethernet

Display & User Interface

Display: Backlit LCD (standard size)

Indicators: 10 LED status (RUN, TRIP, ALARM, FAULT, SERVICE, etc.)

Keypad: Numeric/navigation for local programming

Mechanical & Environmental

Dimensions: 177.5 mm H × 128.5 mm W × 119 mm D

Mounting: DIN rail or panel mount

Enclosure: Flame‑retardant plastic; IP50 (front), IP20 (overall)

Operating Temp: -40°C to +70°C

Storage Temp: -40°C to +85°C

Humidity: 5–95% non‑condensing

Conformal Coating: Yes (protection against dust, moisture, chemicals)

Certifications: UL, CE, CSA, ATEX, IEC 60255

Metering & Diagnostics

Metering: 3‑phase current/voltage, power, energy, frequency, PF, demand

Diagnostics: Event log (512 events), fault recorder, oscillography, pre‑trip data

Thermal Modeling: RTD biasing, cooling time constants, start inhibit

Core Functions

Comprehensive Motor Protection: Detects electrical/thermal/mechanical faults (jam, torque) to prevent damage。

Precision Monitoring: Real‑time tracking of electrical parameters and winding temperature via RTDs。

Harsh Environment Reliability: Conformal coating for chemical, moisture, and dust resistance。

Flexible Control: Configurable start/stop logic, overload curves, and fault responses.

SCADA Integration: Modbus RTU over RS‑485 for remote monitoring/control.

Applications

Oil & Gas: Offshore/onshore pumps, compressors, fans (high humidity/corrosion)

Chemical/Petrochemical: Corrosive process areas, aggressive environments

Metallurgy: Steel mills, heavy‑duty process motors (dust/vibration)

Water Treatment: Coastal/industrial wastewater (moisture/salt)

Mining: Mineral processing motors (dust/humidity)

Usage & Maintenance

Installation: Mount on DIN rail/panel; wire CT/VT, control power, RTDs, and communications.

Programming: Use front keypad or connect to EnerVista 469 software via RS‑232.

Configuration: Set CT/VT ratios, protection curves, RTD types, and I/O mapping.

Maintenance: Inspect terminals annually; update firmware periodically; verify settings after system changes; conformal coating requires no routine maintenance.


Get a Quote