SR469-P5-HI-A20-E (GE Multilin 469 Motor Management Relay)
Description
Model Interpretation
SR469: 469 series motor management relay (draw‑out, modular platform)
P5: 5 A CT secondary phase current input
HI: High‑impedance wide‑range control power (70–265 VAC / 90–300 VDC)
A20: 4 isolated 4–20 mA analog outputs
E: Enhanced front panel (larger LCD, no Ethernet)
Technical Parameters
Input & Power
CT Input: 5 A phase (5 channels); 2 ground CT inputs
VT Input: 0–690 V (delta/wye configurable)
Control Power: 70–265 VAC / 90–300 VDC, 48–62 Hz
Power Consumption: 5–15 W typical
Protection & Timing
Protection Functions: Overload (thermal memory), short circuit, ground fault, stall, undervoltage/overvoltage, phase loss/reversal, RTD overtemperature
Overcurrent Curves: IEC 60255‑3 inverse / definite time, 0.1–10×In
Trip Time: ≤10 ms (instantaneous); ±50 ms accuracy
I/O & Interfaces
Analog Outputs: 4 × 4–20 mA, isolated
Digital Inputs: 9 opto‑isolated (dry/wet contact, ≤1 ms response)
Relay Outputs: 6 Form C (5 A / 250 VAC)
RTD Inputs: 3‑wire; 100Ω Pt, 100/120Ω Ni, 10Ω Cu
Communication: RS‑232 (front, programming), RS‑485 (Modbus RTU); no Ethernet
Display & User Interface
Display: Enhanced 40‑character backlit LCD
Indicators: LED status (RUN, TRIP, ALARM, FAULT)
Keypad: Numeric/navigation for local programming
Mechanical & Environmental
Dimensions: 177.5 mm H × 128.5 mm W × 119 mm D
Mounting: DIN rail or panel mount
Enclosure: Flame‑retardant plastic; IP50 (front), IP20 (overall)
Operating Temp: -40°C to +60°C
Storage Temp: -40°C to +85°C
Humidity: 5–95% non‑condensing
Certifications: UL, CE, CSA, ATEX, IEC 60255
Metering & Diagnostics
Metering: 3‑phase current/voltage, power, energy, frequency, PF, demand
Diagnostics: Event log (512 events), fault recorder, oscillography, pre‑trip data
Thermal Modeling: RTD biasing, cooling time constants, start inhibit
Core Functions
Comprehensive Motor Protection: Detects electrical/thermal faults to prevent damage and downtime.
Precision Monitoring: Real‑time tracking of electrical parameters and winding temperature via RTDs.
Flexible Control: Configurable start/stop logic, overload curves, and fault responses.
SCADA Integration: Modbus RTU over RS‑485 for remote monitoring/control.
Enhanced Local Operation: Larger LCD for clear diagnostics and programming.
Applications
Oil & Gas: Pumps, compressors, fans (medium‑voltage)
Power Utilities: Plant auxiliaries, substation motors
Metallurgy: Steel mills, heavy‑duty process motors
Chemical/Petrochemical: Critical process motor protection
Water Treatment: Pumps, blowers in municipal/industrial facilities
Usage & Maintenance
Installation: Mount on DIN rail/panel; wire CT/VT, control power, RTDs, and communications.
Programming: Use front keypad or connect to EnerVista 469 software via RS‑232.
Configuration: Set CT/VT ratios, protection curves, RTD types, and I/O mapping.
Maintenance: Inspect terminals annually; update firmware periodically; verify settings after system changes.
Get a Quote