GE Fanuc IC697CPX772 (Series 90-70 High-End CPU)
Description
Model Interpretation
IC697: Series 90-70 PLC system
CPX: High-performance CPU with extended communication
772: 96 MHz, 512 KB RAM, 256 KB flash, 3 serial ports
Technical Parameters
Processor & Performance
CPU: 32-bit Intel 80486DX4
Clock Speed: 96 MHz
Boolean Speed: 0.4 µs per boolean instruction
User Memory: 512 KB battery-backed RAM
Flash Memory: 256 KB non-volatile (program storage)
I/O Capacity:
Discrete: 2,000 I/O points (combined in/out)
Analog: 8,000 words (combined in/out)
Floating-Point Math: Supported
Communication
Onboard Ports:
Port 1: RS-232 (RJ11)
Port 2: RS-485 (9-pin D-sub)
Port 3: RS-485 (9-pin D-sub)
Protocols: SNP/SNP-X, Modbus RTU (master/slave), Break-Free SNP
Electrical
Power: +5 VDC, 3.1 A (from 90-70 backplane)
Battery: Lithium (IC697ACC701), 5-year shelf life
RTC: Battery-backed, ±3.5 sec/day max drift
Mechanical & Environmental
Dimensions (H×W×D): 100 × 40 × 160 mm (1 slot)
Weight: ~0.68 kg
Operating Temp: 0°C to +50°C
Storage Temp: -40°C to +85°C
Humidity: 5–95% non-condensing
Certifications: UL, CE, CSA
Internal Resources
Discrete Global Bits: 8,192
Timers/Counters: 2,048
Program Blocks: Up to 512
Diagnostic LEDs: OK, RUN, EN, MEM PROTECT, COMM1/2/3
Switch: 3-position RUN/STOP/LOCK
Core Functions
High-Speed Complex Control: Executes large ladder logic, function block, and structured text programs with floating-point math.
Large I/O Management: Controls up to 2,000 discrete and 8,000 analog points for big process systems.
Multi-Port Communication: Simultaneous connection to HMI, SCADA, and Modbus devices via three serial ports.
Data Security: Battery-backed RAM + flash protects programs/data during power loss.
System Diagnostics: Front-panel LEDs and fault logging for quick troubleshooting.
Applications
Process Control: Power plants, water treatment, oil/gas, chemical, pharmaceutical.
Heavy Manufacturing: Automotive, steel, metalworking, large assembly lines.
OEM Equipment: Printing, textiles, plastics, packaging machinery with complex control needs.
Critical Infrastructure: Tunnel, airport, and building automation requiring high reliability.
Usage & Maintenance
Installation: Plug into any Series 90-70 baseplate CPU slot (single slot); secure with screws.
Programming: Use Proficy Machine Edition or VersaPro.
Battery Replacement: Replace every 3–5 years (IC697ACC701) to avoid data loss.
Compatibility: Works with all Series 90-70 I/O and Genius I/O modules; not compatible with 90-30/RX3i.
No Jumpers: Configuration via software only (no DIP switches).
Get a Quote