GE Amonis IC695CRU320 (PACSystems RX3i Redundant Central Processor)
Description
Model Interpretation
IC695: PACSystems RX3i PLC series
CRU: Control Redundancy Unit
320: High-end 1 GHz performance, redundancy-enabled
Technical Parameters
Processor & Performance
CPU: Intel Celeron M (32-bit) @ 1.0 GHz
Boolean Speed: 0.047 ms / 1K bool instructions
User Memory: 64 MB battery-backed RAM + 64 MB flash NVRAM
Program Blocks: Up to 512 blocks, max 128 KB/block
I/O Capacity:
Discrete: 32K bits (%I/%Q)
Analog: Configurable up to 32K words (%AI/%AQ)
Redundancy Switchover: Min 3.133 ms, max 1 logic scan
Communication
Onboard Ports:
Port 1: RS-232 (SNP slave, Modbus RTU slave)
Port 2: RS-485 (SNP, Modbus RTU, Serial I/O)
Backplane: Dual bus (RX3i PCI + high-speed serial)
Network: Ethernet via rack-mounted modules (no onboard LAN)
Electrical
Power: +3.3V @ 1A, +5V @ 1.2A (from RX3i backplane)
Battery: Lithium battery for RAM retention (replace every 3–5 years)
Mechanical & Environmental
Dimensions (W×H×D): 40 × 100 × 160 mm (2 slots wide)
Weight: ~1.0 kg
Operating Temp: 0°C to +60°C
Storage Temp: -40°C to +85°C
Humidity: 5–95% non-condensing
Certifications: UL, CE, CSA
Internal Resources
Floating-Point Math: Supported
Real-Time Clock (RTC): ±2 sec/day max drift
Diagnostic LEDs: CPU OK, RUN, Outputs Enabled, I/O Force, Battery, Sys Flt, COM1/COM2
Core Functions
Hot-Standby Redundancy: Pairs with IC695RMX128 memory exchange module for real-time data sync; failover in <100 ms.
High-Speed Logic Execution: Complex ladder logic, function block, and C programming support.
Large-Scale I/O Control: Manages up to 32K discrete and 32K analog points for mid-to-large systems.
Dual Serial Communication: Connects to HMI/SCADA, programming tools, and Modbus devices simultaneously.
Data Integrity: Battery-backed RAM + non-volatile flash protects programs/data during power loss.
Applications
Critical Process Control: Oil/gas, chemical, pharmaceutical (zero downtime required)
Power & Utilities: Power plants, water treatment, pump stations
Manufacturing: Automotive assembly, packaging lines, material handling
Infrastructure: Airport systems, rail control, building automation
OEM Equipment: High-reliability machinery with redundancy requirements
Usage & Maintenance
Installation: Requires 2 adjacent RX3i backplane slots (e.g., IC695CHS012/016).
Redundancy Setup: Pair two CRU320 CPUs with one RMX128 module for master-standby configuration.
Programming: Use Proficy Machine Edition (v9.0+).
Battery Replacement: Replace every 3–5 years to prevent data loss.
Compatibility: Works with all RX3i I/O modules; not compatible with Series 90-30/90-70.
Key Differences from IC695CPU320
CRU320: Redundancy-enabled (hot-standby), 2 slots, paired with RMX128
CPU320: Standard non-redundant, 1 slot, lower cost for non-critical systems
Get a Quote