GE IS220PDOAH1A (PDOA – Discrete Output Pack)
Description
Model Interpretation
IS220: GE Mark VIe series distributed I/O module platform
PDOA: Discrete Output Pack (core function: relay-based discrete output control)
H: Hardware revision level
1A: Configuration variant, connector pinout, and firmware revision code
Technical Parameters
Electrical Specifications
Power Supply: 24 VDC (18–32 VDC) via backplane
Power Consumption: ~5 W typical (varies with load)
Output Channels: 12 isolated relay channels
Output Rating: 32 VDC / 3.15 A per channel
Isolation Voltage: ≥500 Vrms between channels and ground
Response Time: <1 ms (Ethernet command to output)
Communication Interfaces
Ethernet: 2 × 10/100 Mbps RJ45 ports (redundant I/O networks)
Protocols: SRTP, Ethernet/IP, IONet (Mark VIe proprietary)
Memory: 4 MB Flash (firmware) + 8 MB RAM (data)
Mechanical & Environmental
Dimensions (H×W×D): 82.6 × 38.1 × 133.4 mm (3.25 × 1.5 × 5.25 in)
Weight: ~0.34 kg (0.75 lbs)
Operating Temperature: -25°C to +70°C
Storage Temperature: -40°C to +85°C
Humidity: 5–95% non-condensing
Protection Class: IP20 (rack-mounted)
Certifications: CE, UL, CSA, HazLoc (Class I, Div. 2)
Front Panel Features
4 status LEDs: Power, Attention, Tx/Rx, Link
2 × RJ45 Ethernet ports
1 × 24 VDC power connector
Core Functions
Redundant Output Control: Controls up to 12 field devices via isolated relays; supports simplex, DMR, and TMR architectures.
Network Redundancy: Dual Ethernet ports enable seamless failover between I/O networks, eliminating single points of failure.
Feedback Monitoring: Accepts terminal board-specific feedback signals for closed-loop control and fault verification.
Built-in Protection: Integrates overload, overcurrent, and overtemperature protection to safeguard modules and field devices.
Hot-Swap Capability: Supports online replacement without system shutdown, maximizing uptime.
Applications
Power Generation: Gas/steam turbine control (fuel valves, starter motors, lubrication systems).
Oil & Gas: Offshore platforms, compressor stations, and hazardous area installations.
Industrial Automation: Petrochemical plants, steel mills, and critical machinery control.
Process Control: Boiler systems, water treatment, and manufacturing line automation.
Usage & Maintenance Instructions
Installation: Plug into standard Mark VIe I/O rack; secure with faceplate screws; ensure proper ventilation.
Wiring: Use shielded cables for Ethernet; separate low-voltage I/O from high-voltage wiring.
Configuration: Set network parameters via ControlST software; assign output channels to control logic.
Maintenance: Inspect connectors for dust/corrosion; check LED status; update firmware annually.
Compatibility: Works with six discrete output terminal boards (SRLY, TRLY series); compatible with Mark VIe IS200/IS210 series modules.