RELIANCE 57C417  AutoMate Interface Module
June 01, 2026

RELIANCE 57C417 AutoMate Interface Module

The RELIANCE 57C417 is an AutoMate Interface Module for the AutoMax/DCS 5000 control platform, designed to bridge AutoMax systems with Reliance AutoMate PLCs. It uses a single‑slot rack‑mount form factor, features dual‑port memory, and supports up to four concurrent processor interfaces. The module delivers stable, protocol‑transparent data exchange in harsh industrial environments.

Description

Product Overview

The RELIANCE 57C417 is an AutoMate Interface Module for the AutoMax/DCS 5000 control platform, designed to bridge AutoMax systems with Reliance AutoMate PLCs. It uses a single‑slot rack‑mount form factor, features dual‑port memory, and supports up to four concurrent processor interfaces. The module delivers stable, protocol‑transparent data exchange in harsh industrial environments.

Model Definition

  • RELIANCE: Brand (Reliance Electric, now part of ABB).

  • 57C: AutoMax system/I/O series.

  • 417: Model code for the AutoMate Interface Module.

    Compatible with standard AutoMax racks and firmware.

Technical Parameters

  • Power: +5V @ 2.5A; +12V @ 0.053A (backplane‑supplied).

  • Communication: RS‑232 physical layer; AutoMate protocol; AutoMate 40E register mapping.

  • Operating Temperature: 0°C to 60°C.

  • Humidity: 5%–90% non‑condensing.

  • Indicators: 7‑segment LED (fault codes); green OK LED (status).

  • Configuration: Front‑panel DROP NUMBER thumbwheel switch.

  • Mounting: Single‑slot AutoMax rack (any non‑processor/non‑common‑memory slot).

Interface & Communication

  • Rear: AutoMax backplane connector (power + internal bus).

  • Front: RS‑232 port for connection to AutoMate PLCs.

  • Function: Bidirectional protocol conversion between AutoMax internal bus and AutoMate PLC protocol; data mapping via dual‑port memory.

Core Functions

  • Connects AutoMax controllers to Reliance AutoMate PLCs.

  • Enables high‑speed, reliable bidirectional data exchange.

  • Supports up to four processor interfaces via dual‑port memory.

  • Provides real‑time status and fault diagnostics via LEDs.

  • Simplifies network node addressing via drop‑number setting.

Application Scenarios

  • Industrial automation lines (metallurgy, paper, chemical, power, machinery).

  • AutoMax–AutoMate integrated control systems.

  • Retrofits of legacy Reliance Electric equipment.

  • Distributed control networks requiring cross‑platform PLC communication.

Operation & Maintenance

  • Installation: Power off rack; insert into empty slot; secure backplane connection.

  • Configuration: Set drop number via front thumbwheel; configure RS‑232 parameters (baud, parity) in AutoMax software.

  • Maintenance: Keep RS‑232 port clean; monitor OK LED and fault codes; replace with identical model if failed.

  • Warnings: Do not disassemble; avoid moisture/dust; ensure proper grounding.