HONEYWELL 51204126-915 DCS Analog I/O Module
Description
Model Number Explanation
51204126: Honeywell DCS analog I/O series
915: Variant with 16‑channel isolated analog output, 0–20mA, group‑isolated (4×4 channels)
Technical Specifications
Channel Configuration: 16 analog output channels, galvanically isolated in 4 groups of 4
Output Signal: 0–20mA (per channel), point‑to‑chassis isolation
Isolation Voltage: 1500VAC (channel‑to‑chassis)
Power Supply: 24VDC (18–30VDC), ≤120mA
Operating Temperature: 0°C to +60°C
Storage Temperature: −40°C to +85°C
Humidity: 5%–95% non‑condensing
Dimensions: 190 × 120 × 30mm
Weight: ≈0.85kg
Certifications: CE, UL 508, RoHS
Interface & Configuration
Connectors: Front‑edge screw terminals (field wiring); DIN 41612 backplane connector
LED Indicators: Module Run, Fault, Channel Status (per group)
Redundancy: Supports dual‑module redundant pairing (1:1)
Diagnostics: Open/short‑circuit detection, overrange, supply voltage monitoring
Key Features
16‑Channel Isolated AO: 4 groups × 4 channels, full galvanic isolation
High Accuracy: ±0.15% FS (25°C), ±0.3% FS (−10°C to +60°C)
Low Drift: ≤50ppm/°C
Robust Protection: Overcurrent, short‑circuit, ESD/surge protection
Hot‑Swap: Online replacement without system shutdown
Coated PCB: Conformal coating for harsh environments (dust, moisture)
Applications
Systems: Honeywell Experion PKS C200/C300, TDC3000, FSC safety systems
Industries: Power generation, oil & gas, chemical, petrochemical, pharmaceuticals
Use Cases: Analog actuator control (valves, dampers), process loop control, safety I/O distribution
Compatibility
Racks: Honeywell 8‑slot/16‑slot DCS I/O racks (200mm depth)
Controllers: C200, C300, TDC3000, FSC 10000‑series
Firmware: Experion PKS ≥ R500; FSC ≥ v2.78
Get a Quote