Honeywell 51199930-100(SPS5713)
June 01, 2026

Honeywell 51199930-100(SPS5713)

Product Introduction The 51199930-100 (SPS5713) is a main power rack/backplane for Honeywell Experion PKS Series C (C300) systems. It provides mechanical mounting and electrical interconnection for up to four SPS5710 (51199929-100) power supplies, distributing 24VDC to controllers and I/O modules.

Description

Model Explanation

  • 51199930: Base part number (SPS5713 series)

  • ‑100: Standard main power rack version

  • SPS5713: Honeywell internal model (System Power Supply Rack)

  • Compatible PSUs: 51199929-100 (SPS5710, 100W) ×4 max

Technical Parameters

  • Device Type: Power distribution backplane/rack

  • Compatibility: Honeywell Experion PKS C300, Series C I/O

  • Input (to rack): 100–240 VAC, 47–63 Hz

  • Output (to system): 24–26 VDC, 20A max

  • Redundancy: Supports 1+1 or N+1 (up to 4 PSUs)

  • Operating Temp: 0 °C to +60 °C

  • Dimensions (W×H×D): 483 mm × 88 mm × 300 mm (19" 2U)

  • Weight: ≈4.5 kg

  • Certifications: CE, UL, CSA, FM (Class I Div 2), RoHS

Interface & Configuration

  • AC Input Terminal: 3‑pin (L/N/PE)

  • DC Output Bus: Backplane distribution to I/O racks

  • PSU Slots: 4 slots for SPS5710 (51199929-100)

  • Status Indicators: Power, Fault, DC OK

  • Alarm Contacts: Dry contacts for system monitoring

Core Functions

  • Power Distribution: Centralized 24VDC distribution for C300 systems

  • Redundancy Support: Seamless failover with 1+1 or N+1 PSU config

  • Hot‑Swap: Replace PSUs without system shutdown

  • Overcurrent Protection: Built‑in fusing per PSU slot

  • Thermal Management: Optimized airflow for high‑density operation

Application Scope

  • Honeywell Experion PKS C300 controller cabinets

  • Series C I/O racks (8‑series I/O system)

  • Process industries: oil & gas, refining, chemical, power

  • Critical control rooms requiring 24/7 high availability

  • New installations or retrofits replacing older SPS5713 racks

Operation & Maintenance

  • Mount in standard 19" cabinet (2U height)

  • Connect AC input to mains; ensure proper grounding

  • Install up to 4 SPS5710 PSUs into slots (active‑active)

  • Verify “DC OK” LED on; “Fault” LED off normally

  • Use only Honeywell‑certified PSUs (51199929-100)


Get a Quote