Honeywell 51198947-100K
June 01, 2026

Honeywell 51198947-100K

Product Introduction The 51198947-100K is a HPM Power Supply Assembly (OEM model SP724-Y01A / ACX631) for Honeywell TDC3000/TPS UCN systems. It’s a fully compatible, functionally identical variant of the standard 51198947-100, often used as a spare/replacement part in DCS cabinets.

Description

Model Explanation

  • 51198947: Base HPM power supply part number

  • ‑100: Standard version (115/240VAC, 550W)

  • K: Kit/Spare Part designation (same hardware, different Honeywell part numbering for spare-parts ordering)

  • Alternate PN: SP724-Y01A (internal assembly number)

  • Equivalent: 51198947-100 / 51198947-100B (drop‑in replacement)

Technical Parameters (Same as 51198947-100)

  • Device Type: AC/DC power supply with 48VDC battery charger

  • Compatibility: Honeywell TDC3000/TPS, UCN (PM/APM/HPM)

  • Input Voltage: 85–264 VAC (auto‑select) or 48VDC battery

  • Output Voltage: 25.25 VDC @10A (AC); 24.25 VDC (battery)

  • Output Power: 550W max

  • Frequency: 50/60 Hz

  • Cooling: Convection‑cooled

  • Protection: Overload, short‑circuit, overvoltage

  • Operating Temp: ‑20 °C to +55 °C (full load)

  • Dimensions (W×H×D): 217 mm × 127 mm × 300 mm

  • Weight: ≈5 kg

  • Certifications: CE, UL, CSA

Interface & Communication Configuration

  • AC Input: IEC C13 (115/240VAC)

  • DC Output: Terminal block (25VDC, 10A)

  • Battery Port: 48VDC charging interface

  • Status LEDs: Power, Output, Battery, Fault

  • Sync Output: 6 VAC @35 mA (line‑frequency sync)

Core Functions

  • Regulated 25VDC: Stable power for UCN controllers/I/O

  • 48V Battery Charging: Integrated charger for backup systems

  • Wide‑Range AC Input: Global mains compatibility

  • Redundant Operation: Supports parallel connection for redundancy

  • Drop‑In Replacement: 100% compatible with -100 / -100B

Application Scope

  • Honeywell TDC3000/TPS DCS (UCN PM/APM/HPM cabinets)

  • Process industries: power, oil & gas, refining, chemical

  • Critical control rooms with 24/7 battery‑backed operation

  • Direct replacement for 51198947-100 or 51198947-100B

Operation & Maintenance Instructions

  • Mount in clean, ventilated cabinet (ambient <55°C)

  • Connect IEC C13 to AC mains; DC output to UCN backplane

  • Connect 48V battery to charge port for backup

  • Verify “Power”/“Output” LEDs on; “Fault” LED off

  • Use only Honeywell‑certified 51198947-100K replacements


Get a Quote