Honeywell 51198947-100B
June 01, 2026

Honeywell 51198947-100B

Product Introduction The 51198947-100B is a revised, backward-compatible version of the 51198947-100 (ACX631) HPM/PM Power Supply for Honeywell TDC3000/TPS UCN systems. It provides regulated 25VDC power with integrated 48VDC battery charging, with minor hardware/PCB upgrades for reliability.

Description

Model Explanation

  • 51198947: Base part number (HPM/PM Power Supply)

  • ‑100: Standard version (115/240VAC, 550W)

  • B: Revision B (component upgrades, PCB tweak, full form/fit/function compatible with -100)

  • ACX631: Internal model (Cherokee International OEM)

Technical Parameters (Same as 51198947-100)

  • Device Type: AC/DC power supply with 48V battery charger

  • Compatibility: Honeywell TDC3000/TPS, UCN (PM/APM/HPM)

  • Input Voltage: 85–264 VAC (auto‑select) or 48VDC battery

  • Output Voltage: 25.25 VDC @10A (AC); 24.25 VDC (battery)

  • Output Power: 550W max

  • Frequency: 50/60 Hz

  • Cooling: Convection‑cooled

  • Protection: Overload, short‑circuit, overvoltage

  • Operating Temp: ‑20 °C to +55 °C (full load)

  • Dimensions (W×H×D): 217 mm × 127 mm × 300 mm

  • Weight: ≈5 kg

  • Certifications: CE, UL, CSA

Key Differences (‑100B vs ‑100)

  • PCB Revision: Updated layout for better thermal performance

  • Capacitors: Industrial‑grade, longer life (10-year vs 5-year)

  • Connectors: Gold‑plated contacts for corrosion resistance

  • Firmware: Minor fault‑detection logic improvements

  • Compatibility: 100% pin‑to‑pin, drop‑in replacement for -100

Interface & Communication Configuration

  • AC Input: IEC C13 (115/240VAC)

  • DC Output: Terminal block (25VDC, 10A)

  • Battery Port: 48VDC charging interface

  • Status LEDs: Power, Output, Battery, Fault

  • Sync Output: 6 VAC @35 mA (line‑frequency sync)

Core Functions

  • Regulated 25VDC: Stable power for UCN controllers/I/O

  • 48V Battery Charging: Integrated charger for backup systems

  • Wide‑Range AC Input: Global mains compatibility

  • Enhanced Reliability: Revision B upgrades for harsh environments

  • Redundant Operation: Supports parallel connection for redundancy

Application Scope

  • Honeywell TDC3000/TPS DCS (UCN PM/APM/HPM cabinets)

  • Process industries: power, oil & gas, refining, chemical

  • Critical control rooms with 24/7 battery‑backed operation

  • Direct replacement for 51198947-100 or 51109684-100

Operation & Maintenance Instructions

  • Mount in clean, ventilated cabinet (ambient <55°C)

  • Connect IEC C13 to AC mains; DC output to UCN backplane

  • Connect 48V battery to charge port for backup

  • Verify “Power”/“Output” LEDs on; “Fault” LED off

  • Use only Honeywell‑certified 51198947-100B replacements


Get a Quote