Honeywell 51198947-100
June 01, 2026

Honeywell 51198947-100

Product Introduction The 51198947-100 (model ACX631) is a high‑performance HPM/PM Power Supply for Honeywell TDC3000/TPS UCN systems. It provides regulated 25VDC power with battery backup charging, designed for industrial control cabinets.

Description

Model Explanation

  • 51198947: Base part number for HPM power supply

  • ‑100: Standard revision (ACX631, 115/240VAC, 550W)

  • ACX631: Official model (HPM/PM Power Supply Assembly)

  • Associated Part: 51109684-100 (compatible reference)

Technical Parameters

  • Device Type: AC/DC power supply with battery charging

  • Compatibility: Honeywell TDC3000/TPS, UCN (PM/APM/HPM)

  • Input Voltage: 85–264 VAC (auto‑select 115/240VAC) or 48VDC battery

  • Output Voltage: 25.25 VDC @10A (AC input); 24.25 VDC (48V battery input)

  • Output Power: 550W max

  • Frequency: 50/60 Hz

  • Cooling: Convection‑cooled

  • Protection: Overload, short‑circuit, overvoltage

  • Operating Temp: ‑20 °C to +55 °C (full load)

  • Dimensions (W×H×D): 217 mm × 127 mm × 300 mm

  • Weight: ≈5 kg

  • Certifications: CE, UL, CSA

Interface & Communication Configuration

  • AC Input: IEC C13 (115/240VAC)

  • DC Output: Terminal block (25VDC, 10A)

  • Battery Port: 48VDC charging interface

  • Status LEDs: Power, Output, Battery, Fault

  • Sync Output: 6 VAC @35 mA (line‑frequency synchronization)

Core Functions

  • Regulated Power: Delivers stable 25VDC for UCN controllers and I/O

  • Battery Charging: Integrated 48V battery charger for backup power

  • Wide Input: Accepts 85–264VAC global mains or 48VDC battery

  • Fault Protection: Overload/short‑circuit/overvoltage protection

  • System Sync: Provides 6VAC line‑frequency sync signal

Application Scope

  • Honeywell TDC3000/TPS DCS (UCN PM/APM/HPM cabinets)

  • Process industries: power, oil & gas, refining, chemical, petrochemical

  • Critical control rooms requiring battery‑backed 24/7 operation

  • Replacement for legacy 51109684-100 power supplies

Operation & Maintenance Instructions

  • Mount in clean, ventilated cabinet (ambient <55°C)

  • Connect IEC C13 to AC mains; connect DC output to UCN backplane

  • Connect 48V battery to charge port for backup power

  • Verify “Power” and “Output” LEDs lit; “Fault” LED off

  • Check battery charge status periodically; replace battery when capacity <60%

  • Use only Honeywell‑certified 51198947-100 replacements