Product Introduction The 51196692-100 is a 5‑Slot Classic CE Chassis for Honeywell TDC3000 / TPS / Experion PKS DCS systems. It serves as a CE‑compliant upgrade to the non‑CE 51195499‑100, housing up to five LCN/UCN control, I/O, or communication modules in a compact, rack‑mountable enclosure.

Description

Model Explanation

  • 51196692: Base part number for 5‑slot classic chassis

  • ‑100: Standard CE‑compliant version (Rev B common)

Technical Parameters

  • Device Type: 5‑slot DCS chassis (backplane + enclosure)

  • Compatibility: Honeywell TDC3000, TPS, Experion PKS (Micro TDC)

  • Slots: 5 front‑loading card slots (LCN/UCN modules)

  • Integrated PSU: 51196653‑100 (5‑slot CE power supply) at bottom

  • Cooling: Right‑side cooling fan assembly (top‑to‑bottom airflow)

  • Backplane: LCN I/O backplane with gold‑finger connectors

  • Dimensions (W×H×D): 483 mm × 222 mm × 406 mm (19” rack, 5U)

  • Weight: Approx. 8.9 kg

  • Certifications: CE (EMC compliant)

  • Operating Temperature: 0 °C to +60 °C

  • Humidity: 5%–95%, non‑condensing

Interface & Communication Configuration

  • Front: 5 card slots with ejectors; status LEDs for PSU/fan

  • Rear: LCN/UCN I/O connectors, power inlet, fan wiring

  • Backplane: Passive LCN bus + power distribution to all slots

  • Power Input: 120/240 VAC (via integrated 51196653‑100 PSU)

Core Functions

  • 5‑Slot Module Housing: Accepts control, I/O, gateway, and history modules

  • Integrated Power & Cooling: Combines PSU, fan, and backplane in one unit

  • CE Compliance: Meets EU EMC directives for industrial installations

  • LCN/UCN Connectivity: Interfaces modules to system networks via rear panel

  • Hot‑Swap Ready: Supports online module replacement (redundant systems)

Application Scope

  • Honeywell TDC3000/TPS/Experion PKS DCS control rooms

  • Process industries: chemical, power generation, oil & gas, refining

  • Compact 19” rack cabinets requiring 5‑slot LCN/UCN node capacity

  • System upgrades replacing non‑CE 51195499‑100 chassis

Operation & Maintenance Instructions

  • Install in standard 19” rack; ensure 5U vertical clearance for airflow

  • Use ESD protection when inserting/removing modules; power off before servicing

  • Verify PSU (51196653‑100) Power OK LED is lit; Fault LED off

  • Clean fan filters monthly; check for loose connectors or damaged backplane pins

  • Avoid overloading slots; use only Honeywell‑certified LCN/UCN modules