Honeywell 51196655-100
June 01, 2026

Honeywell 51196655-100

Product Introduction The 51196655-100 (ACX633, Rev E) is a Dual‑Node Universal AC‑DC Power Supply Module for Honeywell TDC3000 / Experion PKS DCS. It provides isolated, regulated multi‑voltage power to control nodes and I/O cards, serving as a compact, high‑efficiency complement to the 5‑slot/10‑slot file power supplies.

Description

Model Explanation

  • 51196655: Base part number for ACX633 dual‑node power supply

  • ‑100: Standard hardware revision (Rev E)

Technical Parameters

  • Device Type: Dual‑node DCS power supply module

  • Compatibility: Honeywell TDC3000, Experion PKS (control nodes, I/O cards)

  • Input Voltage: 85–265 VAC, 47–63 Hz (universal AC)

  • Output Voltages & Max Current:

    • +5 VDC: 12 A

    • +12 VDC: 5 A

    • −12 VDC: 1 A

    • +24 VDC: 3 A

  • Operating Temperature: 0 °C to +60 °C

  • Humidity: 5%–95%, non‑condensing

  • Dimensions: 320 mm × 220 mm × 80 mm

  • Weight: Approx. 0.76 kg

  • Protection: Overvoltage, overcurrent, short‑circuit, thermal shutdown

  • Certifications: CE, UL

Interface & Communication Configuration

  • Input: AC terminal block (85–265 VAC)

  • Output: Dual isolated DC rails for two control nodes

  • Status Indicators: Power OK, Fault, DC‑OK LEDs on front edge

  • Redundancy: Supports parallel redundant operation with load sharing

Core Functions

  • Dual‑Node Isolated Power: Delivers independent, noise‑isolated power to two nodes

  • Wide‑Range AC Input: Adapts to global industrial voltage standards

  • High Efficiency: Low heat dissipation for long‑term reliability

  • Fault Tolerance: Auto‑shutdown on faults; alarm signaling to host system

  • Hot‑Swap Ready: Can be replaced in redundant systems without downtime

Application Scope

  • Honeywell TDC3000 / Experion PKS DCS control nodes and I/O subsystems

  • Process industries: chemical, power, oil & gas, refining, pharmaceuticals

  • Compact DCS cabinets where 5/10‑slot file supplies are oversized

  • Redundant control systems requiring dual‑node power isolation

Operation & Maintenance Instructions

  • Install with system powered off; follow ESD protection procedures

  • Confirm AC input voltage is within 85–265 VAC range before power‑on

  • Verify Power OK/DC‑OK LEDs are on; Fault LED off in normal operation

  • Periodically clean ventilation slots and connectors; ensure unobstructed airflow

  • Store spares in dry, ESD‑protected environment; avoid extreme temperatures


Get a Quote